Danfoss AK-SM 800A flaws added to CISA KEV (CVE-2025-41450)
At a glance
| Severity | CRITICAL |
|---|---|
| CVSS | CVE-2023-25914: 8.8, CVE-2023-25915: 9.9, CVE-2025-41450: 8.2 |
| EPSS (30-day exploit probability) | CVE-2023-25914: 1.8%, CVE-2023-25915: 2.5%, CVE-2025-41450: 4.3% |
| In CISA KEV (exploited) | Yes, due 2026-11-28, 2026-12-09 |
| Vendor | Danfoss |
| CVE IDs | CVE-2023-25914, CVE-2023-25915, CVE-2025-41450 |
Primary-source details
- CVE-2023-25914: CVSS 8.8 (High), per NVD; a fixed version has not been published; added to the CISA KEV catalog on 2026-11-25, remediation due 2026-11-28.
- CVE-2023-25915: CVSS 9.9 (Critical), per NVD; a fixed version has not been published; added to the CISA KEV catalog on 2026-11-25, remediation due 2026-11-28.
- CVE-2025-41450: CVSS 8.2 (High), per NVD; fixed in danfoss ak-sm 800a firmware: 4.2 (NVD); added to the CISA KEV catalog on 2026-11-25, remediation due 2026-12-09; vendor advisory (listed by NVD).
CISA added three vulnerabilities in the Danfoss AK-SM 800A Series to its Known Exploited Vulnerabilities (KEV) catalog on 25 November 2026, according to the CISA KEV entry. Two of them carry a federal remediation deadline of 28 November 2026 and the third is due on 9 December 2026. Anyone running these Danfoss controllers should treat the Danfoss AK-SM 800A vulnerability set as actively exploited.
What happened
The KEV catalog lists three flaws in the AK-SM 800A Series, each with a different weakness:
- CVE-2025-41450: improper authentication. An attacker can generate a web report that exposes internal IP addresses, usernames and store names.
- CVE-2023-25914: path traversal in the XML interface. An authenticated attacker can read system files on the underlying server.
- CVE-2023-25915: improper input validation. An authenticated remote attacker can run arbitrary commands on the system.
CISA lists known ransomware campaign use as unknown for all three. Who is exploiting them, and against which targets, has not been published.
Am I affected?
NVD records these affected ranges:
- CVE-2025-41450: AK-SM 8xxA firmware prior to 4.2.
- CVE-2023-25914 and CVE-2023-25915: AK-SM 800A firmware up to and including 3.3.
Any unit on firmware older than 4.2 should be considered exposed to at least one of the three. NVD lists version 4.2 as the fixed version for CVE-2025-41450 and links a Danfoss security advisory for it. The two 2023 flaws are described by NVD only with an affected range up to 3.3.
Technical details
| CVE | CVSS (NVD) | CWE | EPSS | KEV due date |
|---|---|---|---|---|
| CVE-2025-41450 | 8.2 High | CWE-305 | 4.3% | 2026-12-09 |
| CVE-2023-25914 | 8.8 High | CWE-22 | 1.8% | 2026-11-28 |
| CVE-2023-25915 | 9.9 Critical | CWE-20 | 2.5% | 2026-11-28 |
All three are reachable over the network. CVE-2025-41450 needs no privileges but requires user interaction and a high-complexity attack, according to its CVSS vector. The two 2023 flaws need a low-privilege account. CVE-2023-25915 has a changed scope, which is why it scores 9.9: a successful command execution can affect more than the vulnerable component.
EPSS, the probability that a flaw will be exploited in the next 30 days, is low for all three (FIRST EPSS). KEV listing is the stronger signal here, because it reflects exploitation that has already been observed.
Why this matters
Analysis, not new facts. The AK-SM 800A is a site management controller used in commercial refrigeration environments. The three flaws chain naturally: an information leak that reveals usernames and internal addresses helps an attacker target the authenticated bugs, and the command execution flaw could give control of the device. Low EPSS scores should not delay action on a KEV-listed product. If a controller is reachable from the internet, patch within hours. If it sits behind a firewall, the risk is mainly from stolen or reused credentials.
How to fix and what to do
- Inventory every AK-SM 800A unit and record its firmware version.
- Update units on firmware below 4.2 to 4.2 or later, following the Danfoss advisory.
- Take management interfaces off the internet. Restrict access to a management VLAN or VPN.
- Rotate credentials on units that may have been exposed, since the information leak reveals usernames.
- For the two 2023 flaws, where NVD gives only an affected range, apply vendor mitigations and ask Danfoss for guidance. CISA’s required action is to apply vendor mitigations or stop using the product if mitigations are unavailable.
- Hunt for signs of abuse: web report requests from unfamiliar addresses, requests to the XML interface that include path traversal sequences such as
../, and unexpected processes or outbound connections from the controller. - Tell facilities and operations teams. These devices are often managed outside normal IT patching cycles.
CISA’s binding directive applies to US federal agencies, but its deadlines are a useful prioritisation guide for everyone else: 28 November 2026 for CVE-2023-25914 and CVE-2023-25915, and 9 December 2026 for CVE-2025-41450.
Related coverage
Sources
- CISA KEV catalog: CVE-2025-41450
- NVD: CVE-2025-41450
- NVD: CVE-2023-25914
- NVD: CVE-2023-25915
- Danfoss security advisory DSA-2025-03-01